Failure Debug and Solution

Items

Failure

Handling Method

1

C1 Compressor over-current tripping.

Check whether the electromagnetic valve switch overload protector in distribution room is tripping. Please press the reset button again.

2

C1 Compressor high voltage tripping.

Open the cover below the body and check whether the high voltage protector switch is

tripping. Please press the reset button again.

3

C2 over-current tripping.

Check whether the electromagnetic valve switch overload protector in distribution room is tripping. Please press the reset button again.

4

C2 high voltage tripping.

Open the cover below the body and check whether the high voltage protector switch is tripping. Please press the reset button again.

5

Abnormal temperature control.

Check whether the fan inside is running. If the fan motor is burn out please inform us to replace it

Check whether the humidifier over-temperature protector is set improperly. If the protector isn’t in proper position please reset it.

6

Abnormal power supply.

*Please check if the power supply phase loss or inversion.

*Please check wire is disconnected or not.

7

Inner Chamber over-temperature

Check whether the over-temperature protector is damaged or cannot control. Please inform us to repair.